Condensation Inside a Ceiling Void: Why IP20 Strip Fails There
- 2026-11-23 16:35
- /
- Alan
IP20 means protected against fingers, not against water. A ceiling void above a warm retail floor is one of the wettest places in the building, and the condensation lands on the strip, not on the floor.
A supermarket perimeter cove started failing after eighteen months. The strip was standard IP20 COB on an aluminum channel in a void above the sales floor. When we opened the ceiling, the channel was wet and there were water marks along the top edge of the strip.
How the water gets there
Warm, humid air from the shop floor leaks through downlight cut-outs and service gaps. The concrete slab above is cooler, especially in winter and overnight. Moisture condenses on the first cold surface it meets, which is often the aluminum channel or the strip itself.
In air-conditioned buildings the pattern shifts with the season but does not disappear. During shutdown periods the void sits close to dew point, and the first hour of operation produces a film of water on anything thermally massive.
What IP20 strip does when it gets wet
The failure is rarely immediate. Water reaches the cut ends, the solder pads and the joint between the FPC and the copper bus. Corrosion raises resistance, which raises heat, which accelerates corrosion. On white strip the first symptom is often a brown or green tint at the ends, then flicker, then a dead section.
The adhesive also fails. Pressure-sensitive tape loses grip on a damp surface, and the strip sags away from the channel where it can no longer conduct heat. Once it is off the channel, the LEDs run hotter and the whole chain degrades faster.
What holds up better
- IP65 or IP67 strip with a fully encapsulated FPC, not just a coated top surface.
- Sealed connectors or solder joints protected with neutral-cure silicone.
- Mounting on a channel that is thermally coupled to the strip and not to the cold slab.
- Keeping the strip off the coldest surface; a small air gap plus a bracket is better than direct contact with a wet slab.
IP65 silicone coating helps but does not make an IP20 joint waterproof. The weak points are always the ends and the joints, which is why encapsulated strip with sealed ends matters more than the coating on the middle of the reel.
Void ventilation and dew point
If the void has no ventilation, moisture accumulates over weeks and condenses whenever the surface temperature drops below dew point. Adding vents at both ends of a void run allows a slow air exchange and keeps the dew point closer to the space below.
For kitchens, pools and laundries, treat the void as a wet location regardless of what the drawings say. The cost difference between IP20 and IP65 strip is small against opening a finished ceiling twice.
Diagnosing a moisture failure
Look for water marks on the channel, white or green corrosion at the pads, and adhesive that has released in patches. Measure resistance across a suspect section with the power off; a section that reads much higher than its neighbours has corroded.
Replace the affected run rather than cleaning it. Corroded pads do not recover, and a cleaned joint will fail again in the same conditions. Our IP-rated COB ranges are the practical starting point for voids where moisture is expected.