Strip in a Cable Tray: Interference, Spacing and Derating
- 2026-11-23 16:50
- /
- Alan
A cable tray is a shared highway. Lighting feeders are the smallest vehicles on it, and they are the ones that notice the traffic.
A warehouse mezzanine had the 24V strip feeders pulled through a tray already carrying variable-frequency drive output cables and a data trunk. The strip flickered when the conveyors ramped, and the diffusers showed a faint beat at low dim.
What causes the interference
VFD output cables carry high-frequency switching currents. Unshielded lighting cable running alongside picks that up capacitatively, and the driver's input or the control line passes a little of it to the DC output.
The symptom is usually a shimmer or flicker that follows the motor load, not a steady dimming. If the flicker changes when a conveyor starts, the cause is electrical noise, not voltage drop.
Separation that works
- Keep the lighting feeder at least 300 mm from VFD output cables, or use a shielded cable with the screen earthed at the driver end.
- Do not run the 0-10V or DALI control line in the same tray as drive cables without a shielded pair.
- Route data in a separate compartment of the tray where one exists.
- If the tray is crowded, use a separate tray for lighting; it is cheaper than chasing faults later.
Derating and heat
A tray full of cables runs hotter than free air. The lighting feeder in the middle of a loaded tray sees a higher ambient, and the driver mounted on the tray sees it too. Derate the cable and keep the driver off the tray unless it is rated for the temperature.
In summer, a roof-space tray can reach 50°C. A driver at 80% load in that ambient is above its derated capacity, which is a warranty issue before it is a lighting issue.
Fixing and access
Strip mounted inside a tray is hard to clean and hard to replace. Use the tray for the feeder, not for the strip, unless the tray is purpose-made with a diffuser and access.
If the strip must be in the tray, keep it on the underside of the lid or on a bracket, away from cable movement, and leave access at intervals.
What we changed
We moved the strip feeders to a dedicated tray 400 mm away, shielded the control pair, and mounted the drivers on the mezzanine wall rather than on the tray. The flicker stopped and the driver case temperature dropped by 12°C.
Cable specification is part of the same decision. In a public or industrial building the feeder usually has to be low-smoke, zero-halogen and fire-rated to the containment class. A length of ordinary PVC flex pulled through a shared tray is a compliance issue that appears at inspection, long after the tray is full.
Commission with the drives running at several speeds. A flicker that only appears at 40 Hz is still a flicker, and the maintenance team will find it on a Monday morning.
Our drivers list ambient derating, and the COB ranges give the load per metre used to size the feeder.