Short runs are not automatically easy. On shelving, the problem is usually the number of connections, not the length of any one segment.
A supermarket refit had 24 shelf bays, each with a 1.5 m strip under the shelf edge. The contractor daisy-chained four bays per feed, reasoning that 6 m was short. The last bay in each chain was visibly dimmer, and two drivers ran hot.
What the arithmetic shows
Each bay at 10 W/m draws 15 W, or 0.625 A at 24V. Four bays in a chain is 2.5 A through the first bay's tail and connector. Over 6 m the board loss is modest, but the connectors and the tail terminations add up.
With four connector pairs at 0.1 ohm each, that is 0.4 ohm in the path, costing about 1V at 2.5 A. The last bay sees 23V instead of 24V, which is a visible difference on a white shelf edge.
Wiring that avoids it
- Feed each bay, or each pair of bays, from a home run rather than chaining four.
- Use a single driver per gondola run with a short feeder to each bay.
- Keep the feeder in the shelf upright, not looped along the shelf edge where it is visible.
- Terminate with proper connectors rated for the current, not push-on tails.
The driver side
Twenty-four bays at 15 W is 360 W, plus losses. One 400 W driver is marginal; two 250 W drivers split by aisle are better and give fault isolation. On the job the single 400 W driver was running at 90% and heating the shelf void.
Two drivers also halve the inrush on a single circuit, which matters when the whole aisle switches on together at store opening.
Short segments also mean many small loads switching on at once, which is an inrush question rather than a steady-state one. Spread the zones across drivers and check the breaker's magnetic trip.
Shelf-specific details
Shelf edges are cleaned, bumped and loaded. Use a profile with a diffuser and a mechanical fixing; adhesive alone will not survive a year of restocking. Keep the strip away from the shelf lip where trolleys hit it.
Where shelves are re-planogrammed, the strip and feeder must be re-routeable. Home runs with connectors at each bay make that possible; a soldered chain does not.
Commissioning check
Measure the last bay in every chain, not just the first. If the chain was designed as four, check bay four. The difference between bay one and bay four is the number that matters.
Also check the temperature inside the shelf void after an hour. Shelving is often a closed box with the driver and the strip sharing the same warm space. If the void is above 40°C, derate the driver and consider mounting it in the upright rather than under the shelf.