Stairwell Strip With Occupancy Sensing: Wiring That Passes a Test
- 2026-11-23 16:47
- /
- Alan
A stairwell is a space people use for twenty seconds. Sensing is there to keep it dark most of the time, and emergency operation is there for the one time it matters.
A residential block had strip on each flight, controlled by microwave sensors at the landings. The lights came on correctly but stayed on for the full delay after the last person left, and the emergency test failed on two flights.
Sensor placement
- Mount the sensor where it sees the flight, not just the landing. People enter at the landing and descend; a sensor pointing at the door misses them.
- Avoid sensors that see through the stairwell wall into the corridor, which keeps the lights on permanently.
- Set the hold time short, 30–60 seconds, and the sensitivity moderate; stairwells have few false triggers.
- Use a sensor rated for the mounting height and the material of the ceiling.
The emergency conflict
Emergency operation requires the strip to illuminate on mains failure regardless of the sensor. That means an unswitched live to the emergency driver or a changeover that bypasses the sensor. If the sensor is in series with the whole circuit, the emergency function cannot work.
On the two failing flights the sensor had been wired ahead of the emergency driver, so a mains failure left the driver without an unswitched feed. The fix was a separate permanent live to the driver, taken from the same circuit before the sensor.
Dimming and standby
Some schemes run a low standby level instead of full off, which helps with safety and camera coverage. That needs a dimmable driver and a sensor with a standby output, not a simple on/off relay.
Standby at 5% is enough to see the steps without defeating the energy saving. Set it by walking the flight at night with only the standby on.
Testing
Simulate a mains failure at the local isolator and confirm each flight illuminates for the rated duration. Then restore and confirm the sensor resumes normal control. Do this per flight, not once for the building.
Record the results by flight and keep the sensor settings in the handover file; the next person to adjust the hold time will otherwise undo the commissioning.
Watch for false triggers from glass doors and from the lift lobby. A microwave sensor that looks through a glazed wall at a moving corridor will hold the flight on permanently, and the energy saving disappears. Adjust the detection zone or change the mounting position rather than reducing sensitivity until it misses people.
Cable routing in a stairwell is usually fire-rated and often surface-mounted, so the sensor cable has to match. Do not run a standard data cable up a protected stair without the specified containment. Test the sensing at night as well.
Our sensor range covers stairwell mounting heights, and the COB strip works with the dimmable drivers used for standby levels.