Emergency lighting is a compliance item, not a lighting preference. On a long cove the decision is usually whether to put batteries in the ceiling next to each driver or to keep them in one room and run a dedicated circuit.
Two office refits, same strip, same length, different emergency strategy. One used self-contained battery drivers in the cove; the other used a central inverter in the riser. Both passed commissioning. They behave very differently in service.
Self-contained battery drivers
Each emergency driver carries its own battery and changeover circuit. Wiring is simple: the same switched live plus an unswitched live for charging, and the driver senses loss of supply and switches to battery.
Advantages: no central single point of failure, no dedicated distribution, and each fitting is independently testable. Disadvantages: batteries sit in the warmest part of the building, which shortens life; a 30 m run needs several units, and each one is another device to test and replace.
Battery life in a 45°C cove is the weak point. NiCd and NiMH packs that would last four years at 25°C often fail in two. Specify the battery chemistry and the ambient rating, and record the installation date on each unit.
Central inverter
A central inverter converts DC to AC or feeds a dedicated emergency circuit from a battery bank in a service room. The cove keeps ordinary drivers; the inverter supplies them through a separate emergency circuit.
Advantages: batteries live in a controlled environment, one system to maintain, and the test regime is centralised. Disadvantages: a dedicated circuit to every zone, a single point of failure, and the inverter must be sized for the connected emergency load plus diversity.
On a 30 m cove at 7 W/m, the emergency load may be 210 W plus driver losses. A 500 W inverter with a 90-minute rating covers it, but only if the emergency circuit actually feeds that zone and not the whole floor.
What the standards expect
Emergency lighting needs to operate for the rated duration, typically 90 minutes, at a defined output. Not every luminaire on a circuit has to be emergency; the design usually calls for a proportion along the escape route. Confirm the required illuminance and duration with the project's lighting designer rather than assuming the whole cove must stay lit.
Testing is part of the system: a monthly functional test and an annual duration test, with results recorded. Self-contained units with automatic test functions reduce labour but still need the records.
Practical selection
- Small zones, hard-to-reach risers, or phased fit-outs: self-contained battery drivers are simpler.
- Large floors with many zones and a maintained service room: central inverter is easier to manage.
- Very warm coves: keep batteries out of the ceiling where possible, which favours the central approach.
- Either way, keep the emergency feed separate from the dimmed feed and label it at the driver.