Feeder Cable Sizing for 30 Metre 24V Runs: When 1.5mm² Is Not Enough
- 2026-11-23 16:26
- /
- Alan
Contractors size the AC feed carefully and then run 0.75 mm² flex to the strip because it came in the box. On a 30 m 24V run drawing 8–9 A, that flex can be a bigger loss than the strip itself.
We surveyed six recent commercial installations last year. In four of them the feeder from driver to strip was 0.75 mm² or 1.0 mm², run 6–12 m through a ceiling void. In two, the feeder accounted for more voltage drop than the first 15 m of strip.
The calculation, with real numbers
Copper resistivity is about 0.0175 Ω·mm²/m at 20°C, rising roughly 0.4% per °C. For a two-conductor feed, the loop resistance is:
Rloop = 2 × 0.0175 × L / A
where L is one-way length in metres and A is conductor cross-section in mm².
| Feeder | 10 m loop R | Drop at 8.75 A | Share of 24V |
|---|---|---|---|
| 2 × 0.75 mm² | 0.47 Ω | 4.1 V | 17% |
| 2 × 1.0 mm² | 0.35 Ω | 3.1 V | 13% |
| 2 × 1.5 mm² | 0.23 Ω | 2.0 V | 8.4% |
| 2 × 2.5 mm² | 0.14 Ω | 1.2 V | 5.1% |
These figures assume the full run current flows through the feeder. Once the feeder splits or injects, downstream current falls and the sums change.
Why 1.5 mm² is often the minimum, not the target
On a 30 m 24V run at 7 W/m, 1.5 mm² over 10 m still costs about 2V before the strip sees anything. That is on top of the strip's own distributed loss, so the far end is already at 8–10% below nominal. Moving to 2.5 mm² halves that and is usually cheaper than adding injection taps.
Above 2.5 mm², the cable gets stiff and hard to dress inside a cove. At that point, the better move is to shorten the DC path — put the driver closer, or go to 48V — rather than keep fattening copper.
Practical selection rules
- Calculate with the full load current, not the driver's nominal rating.
- Use loop resistance (both conductors), not one-way.
- Keep feeder drop under 0.5V on a 24V system where you can.
- Use flexible multi-strand cable rated for the void temperature, not bell wire.
- Fuse or breaker the DC output at the driver; the driver's own protection may not cover a short in a long feeder.
- Do not parallel two different gauges into the same strip; current shares inversely with resistance and the thinner leg runs hot.
A word on connectors and terminations
A 2.5 mm² cable landing on a 22AWG strip pad is a mismatch. The weak point becomes the transition, not the cable. Use a proper distribution block or a solderless connector rated for the wire, and check the joint with a thermal camera after 30 minutes. A warm joint at the strip start with a cold cable behind it means the resistance is at the transition.
For long runs we often bring the feeder to a small DC junction box in the void, then run short 0.5 mm² tails to each strip segment. That keeps the high-current path in large copper and the small connections short.
Cable sizing is the cheapest part of a long-run design and the most commonly skipped. If you are specifying a 24V perimeter now, our strip families list the load per metre you need, and our power supplies cover the driver side of the same calculation.