PSU Headroom in an Enclosed Cove: What 80 Percent Load Looks Like in Summer
- 2026-11-23 16:32
- /
- Alan
Datasheet wattage assumes free air and a sensible ambient. A ceiling void in July is neither. The load that looks comfortable on paper is often the reason a driver fails in its second summer.
We were called to a hotel ballroom where the cove drivers were failing roughly once a year. The as-built drawing showed 210W on 240W drivers — 87.5%, which the contractor considered fine. The drivers sat in a void above a warm ceiling, next to the strip, with no ventilation.
Why the nameplate number is not the working number
Most constant-voltage drivers are rated at 25°C or 40°C ambient and derate above that. A unit rated 240W at 40°C may only be comfortable at 200W at 50°C, and less at 60°C. Electrolytic capacitor life roughly halves for every 10°C rise, so 45°C versus 55°C inside the case is the difference between eight years and four.
The strip adds to that ambient. A 7 W/m COB run dissipates most of its power as heat, and in a closed cove the air around the driver can sit 10–15°C above room temperature. Add the driver's own losses and the local pocket gets warmer still.
The calculation we use
- Sum the strip load: W/m × total metres, plus controllers and sensors on the same driver.
- Apply the driver's derating curve for the measured void temperature, not the room temperature.
- Keep continuous load at 75–80% of derated capacity.
- Keep separate margin for inrush, especially with several drivers on one breaker.
On the ballroom job the void measured 48°C at 4 pm. The 240W driver derated to roughly 190W. Actual load was 210W. The drivers had been running above their derated capacity every afternoon, which explained the annual failures better than any manufacturing story.
What we changed
We replaced the drivers with 320W units and moved them out of the hottest pocket to a bracket near the void access panel, where air moves. Load dropped from 113% of derated capacity to about 66%. Case temperature fell from 78°C to 54°C. Two summers later there had been no repeat failure.
Moving a driver 2 m is often more effective than buying a bigger one. Heat is the mechanism, and airflow is the fix.
Rules for enclosed commercial coves
- Never design to more than 80% of nameplate unless you have measured the ambient and checked the derating curve.
- Mount drivers where they can be reached and where air is not trapped against the ceiling slab.
- Separate drivers from the strip by at least a short distance; do not bolt them to the same hot aluminum run.
- Use one driver per zone rather than one large driver feeding everything; it reduces both thermal concentration and fault scope.
- Record the loaded output voltage and case temperature at handover, so the next technician has a baseline.
The failure pattern to recognise
Drivers that fail in late summer, after two or three years, with no obvious electrical fault, are usually thermal. The same driver in a ventilated rack lasts far longer. If the case is too hot to hold your hand on — above roughly 60°C — the design has no margin left.
For cove work we normally specify 24V constant-voltage drivers with at least 25% headroom over the connected load, then verify with a thermal probe after 30 minutes. Our power supply range lists derating data you can check against the measured void temperature.