Why a Bigger Power Supply Will Not Fix Far-End Dimming
Your Location: Home - Blog

Why a Bigger Power Supply Will Not Fix Far-End Dimming

  • 2026-11-23 16:26
  • /
  • Alan

The driver is a voltage source, not a pressure pump. Adding capacity lets it deliver more current if the load asks for it, but the load is fixed by the strip. The voltage at the far end is set by the resistance in between, and that resistance does not change when the label on the driver changes.

A facilities team called us after replacing a 24V 240W driver with a 24V 400W driver on a 28 m perimeter run. The tail was still dim. The new driver was also running cooler than the old one, which convinced them the problem was solved until the lights came on that evening.

What the driver actually controls

A constant-voltage driver holds its output terminals at 24V within its regulation band, up to its rated current. If the strip plus wiring draws 8 A, the driver supplies 8 A. Give it a 16 A rating and it still supplies 8 A. The extra headroom only matters when the load approaches the old limit, or when inrush and start-up need margin.

Voltage at the far end is:

Vend = VPSU − IfeederRfeeder − ∫i(x)r(x)dx

None of those terms contain the driver's wattage. They contain current, copper length, copper cross-section and joint resistance.

When a bigger driver does help

There are three legitimate cases. First, the old driver was genuinely overloaded and its output was sagging below 24V at full load — a 24.1V open-circuit reading that falls to 22.8V loaded is a real driver problem, not a wiring problem. Second, the installation grew after commissioning and now exceeds the original rating. Third, the driver was running at 95–100% in a hot void, and the upgrade is about thermal margin and lifetime, not brightness.

In all three cases, the test is the same: measure at the driver terminals under load. If it holds 23.8–24.2V, the driver is not your problem.

The trap: a larger driver hides a real fault for a while

On one warehouse job, a 12V system with a 500W supply was dim at 18 m. The team added a second 500W supply in parallel at the same end. Brightness improved slightly, because the paralleled supplies held 12.1V instead of 11.8V under load, and everyone declared it fixed. Six months later two joints failed. The underlying issue — a 12V run far too long for its copper — had never been addressed, and the marginal voltage gain masked rising joint resistance.

What to do instead

  • Measure first. Driver terminals, strip start, midpoint, far end, all under load and after warm-up.
  • If the drop is in the feeder, go up one or two gauge sizes before touching the driver.
  • If the drop is in the strip, shorten the electrical path: dual-end feed, centre feed, or injection taps.
  • If the driver is over 80% loaded, resize it — but resize for margin, and fix the drop separately.
  • If the run is longer than 20 m at 24V, consider 48V strip for the next phase. At the same wattage, current halves and the resistive loss falls to a quarter.

A 48V version of the same COB family is the cleanest answer when the layout allows a new driver. It is not a drop-in swap on an existing 24V circuit: drivers, connectors, controllers and any dimming interface all change with it.

A quick sanity calculation before ordering parts

Take the strip wattage per metre, multiply by the run length, divide by the system voltage to get current. Then estimate the loop resistance of the feed path and the strip trace, and calculate the drop. If the result is above 5% of nominal voltage, no driver change will rescue it. If you want the shortcut, our strip selection pages list W/m and voltage per family, and the COB category covers the models most often used in coves.

Alan
Alan Linear Lighting Application & Product Technical Specialist, ShenZhen Arraystarled Limited
  • Verifies specifications, installation guides and technical support for SMD/COB LED strips, silicone LED neon flex, flexible wall washers, aluminum profiles, LED drivers and DMX512/WLED control solutions.
  • Compiles internal product specification standards and factory burn-in and lighting test procedures; supports on-site selection, power distribution and commissioning for commercial spaces, exhibitions and architectural outlines.
  • Troubleshoots long-run voltage drop and power injection, power supply load headroom calculations, thermal management and aluminum profile selection, and signal polarity or wiring faults.
  • Works with overseas contractors, designers and purchasing teams on voltage, wattage, cutting intervals, IP ratings and control compatibility, reducing rework from sampling to bulk installation.
Recipient of the China Lighting & Lamps Industry Linear Lighting Application Innovation Award and the LED CHINA Commercial Linear Lighting Solution Excellence Award.

Focused on bringing real engineering parameters and field troubleshooting experience into every LED strip technical guide.

Click To Action

Get a free consultation with us!