30m 24V Cove Run Dims at the Far End: What We Found and Fixed
- 2026-11-23 16:26
- /
- Alan
A 30 m 24V run fed from one end looked right for the first 10 m, softened through the middle, and visibly dropped off after 25 m. The feeder at the PSU was warm to the touch. Nothing was broken. The installation was simply asked to carry more current than its copper could carry without losing voltage.
This was a retail interior: a continuous cove around a sales floor, strip mounted on the back of a shelf lip, diffuser on, single 24V driver in a ceiling void about 8 m from one end of the run. The contractor had tested each 5 m reel on the bench and every reel looked fine. On site, the last 5 m looked like a different product.
The numbers we measured
We waited until the strip had run for 30 minutes, because voltage readings taken cold tell you very little. Then we measured at four points with a true-RMS meter, probes on the strip pads, load unchanged.
| Point | Reading | What it told us |
|---|---|---|
| PSU terminals, loaded | 24.1 V | Driver healthy, set correctly |
| Strip start | 23.8 V | 0.3 V lost in the feeder |
| Midpoint, 15 m | 22.4 V | Board and joint losses accumulating |
| Far end, 30 m | 21.2 V | 11.7% below nominal |
An 11.7% drop does not sound dramatic on paper. On a white 24V strip it is obvious on a wall, because light output tracks current, and current tracks voltage on a constant-voltage strip. The last 5 m were doing most of the visible damage.
Why one end cannot carry 30 m
Two resistances sit in series between the driver and the last LED: the feeder conductor, and the strip's own copper traces. The feeder is a single resistance carrying the whole load. The strip is a distributed resistance carrying a current that decreases as you move down the run, which is why the effective drop in the strip is roughly half of what a simple end-to-end calculation suggests.
For a 7 W/m 24V COB strip, each metre draws about 0.29 A. Thirty metres is 8.75 A. If the strip's copper adds up to about 0.6 Ω over the full length, the distributed drop is close to 8.75 × 0.6 ÷ 2 ≈ 2.6 V. Add a feeder losing 0.3–0.5 V under load and you land exactly where we measured.
That is also why the feeder felt warm. 8.75 A through a small conductor dissipates power in the cable, and in a ceiling void with no airflow the jacket temperature climbs. Warm is not automatically a fire risk, but it is a symptom: the same resistance that heats the cable is the resistance dropping voltage to the far end.
Four fixes, and why we picked two of them
Dual-end feeding
Feeding both ends halves the electrical distance from each feed to the middle. On this job the far end had a service gap in the cove, so we could reach it. The catch is that both feeds must be the same length and the same gauge, and the 0V must come from the same source, otherwise the two feeds fight each other and the strip carries unintended current between them.
Mid-run injection
We ran a separate 2-core feeder along the void and tapped at 15 m, fused at the tap. That cut the longest electrical path to about 7.5 m in each direction. Injection is the practical answer when the run is already mounted and cannot be split. It is not free: every tap is a new failure point and must be fused and labelled.
Splitting into two drivers
Two 24V drivers, one per 15 m half, removes the shared feed entirely and gives each zone its own switch and dimming channel. It costs an extra driver and an extra switch leg, but it also means a driver failure takes out half a ceiling, not the whole floor.
A bigger single driver
We did not do this. Raising the PSU from 240 W to 320 W changes nothing at the far end, because the limiter is the resistance between the driver and the LEDs, not the available current. The existing driver was already at roughly 88% of its rating with 210 W of strip on it, which was a separate problem worth fixing.
What we actually built: dual-end feed from one 320 W driver, split into two switch legs, with the PSU loaded to about 66%. The far end came back to 23.5 V under load and the visible gradient disappeared. The feeder temperature dropped by around 9°C.
Commissioning sequence that would have caught it
- Measure the loaded output at the PSU, not the open-circuit voltage.
- Measure at the strip start, the midpoint and the last metre, after 30 minutes of run time.
- Compare the far-end reading against the strip's rated voltage. More than about 5% is worth acting on; 10% is a defect.
- Touch the feeder and every joint after the run. Any joint noticeably warmer than its neighbours is a resistance problem.
- Record the numbers in the handover file so the next person is not guessing.
If you are laying out a long 24V cove now, the decision to make before mounting is where the power enters. Bringing the feed to the middle, or planning injection points on the drawing, costs almost nothing at design stage and saves a rework visit later. Our COB strip range lists the watt-per-metre figures you need for that calculation, and the 5mm free-cut COB is the model we used on this run.